Browse Categories

Altronix AL600ULM Power Supply

Altronix AL600ULM Power Supply
Item #: 060-0400

Product Info

Altronix

Altronix AL600ULM Power Supply with Fire Alarm Disconnect, Input 115VAC 60Hz at 3.5A, 5 PTC Outputs, 12/24VDC at 6A, Grey Enclosure, Lifetime Warranty

This unit converts a 115VAC, 60Hz input into 5 individually protected Class 2 Rated power limited 12VDC or 24VDC outputs. Each output will route power to a variety of access control hardware devices including Mag Locks, Electric Strikes, Magnetic Door Holders, etc.

These outputs will operate in both Fail-Safe and Fail-Secure modes. Controlled trigger input is achieved through normally open (N.O.) or normally closed (N.C.) supervised input or the polarity reversal from an FACP (Fire Alarm Control Panel). A form “C” dry output relay enables HVAC Shutdown, Elevator Recall or it may be used to trigger auxiliary devices.

Specifications:

Input:
115VAC, 60Hz, 3.5A.
Input fuse rated @ 3.5A/250V.
Fire Alarm Panel or Access Control System trigger inputs. N.O. or N.C.supervised trigger input and polarity reversal trigger input.

Output:
12VDC or 24VDC selectable outputs.
6A supply current.
5 PTC protected Class 2 Rated power limited outputs, rated @ 2A (auto resettable).
Output relay energizes when unit is triggered (form “C” contact rated 1A @ 28VDC).
Filtered and electronically regulated output.
Short circuit and thermal overload protection.

Battery Backup:
Built-in charger for sealed lead acid or gel type batteries.
Automatic switch over to stand-by battery when AC fails.

Supervision:
AC fail supervision (form “C” contacts).
Notification trigger is selectable for 30 seconds (factory set) or 6 hours.
Low battery supervision (form “C” contacts).
Battery presence supervision (form “C” contacts).
Power fail supervision relay (form “C” contacts).

Visual Indicators:
AC input and DC output LED indicators (power supply board).
Red LEDs indicate condition of power outputs (multi-output board).
Power & input trigger LEDs (multi-output board).

Temperature:
Operating: 0 C to 49 C (32 F to 120 F).
Storage: – 20 C to 70 C ( – 4 F to 158 F).
Relative Humidity 85% +/- 5%.
BTU/Hr (approx.):12VDC: 37 BTU/Hr. – 24VDC: 74 BTU/Hr.
System AC input VA requirement: 166.75VA.

Enclosure:
Wall mount enclosure for indoor use.
Accommodates up to two (2) 12VDC/7AH Batteries.

Dimensions:
13“W x 13.5“H x 3.25“D (330 mm W x 343 mm H x 83 mm D).
1/2” and 3/4” combination knockouts.

Product Weight: 7.9 Lbs. (3.583 kg). – Shipping Weight: 8.9 Lbs. (4.036 kg).

Item Specifications

  • 14.75 lbs per EA
In Stock at Various Locations
QTY:

Have Questions?

Ask our experts: